{"id":210893,"date":"2026-11-01T01:54:10","date_gmt":"2026-11-01T01:54:10","guid":{"rendered":"https:\/\/www.europesays.com\/korea\/210893\/"},"modified":"2026-11-01T01:54:10","modified_gmt":"2026-11-01T01:54:10","slug":"south-koreas-kt-cloud-recreates-140kw-heat-load-without-gpus-brings-aidc-design-tech-in-house-biggo-finance","status":"publish","type":"post","link":"https:\/\/www.europesays.com\/korea\/210893\/","title":{"rendered":"South Korea&#8217;s KT Cloud Recreates 140kW Heat Load Without GPUs, Brings AIDC Design Tech In-House \u2014 BigGo Finance"},"content":{"rendered":"<p>KT Cloud is independently validating the cooling and power technologies at the heart of next-generation AI data centers (AIDCs) at its &#8220;AI Innovation Center&#8221; in the Mokdong 2 Data Center in Yangcheon District, Seoul. The key achievement is that the company developed its own test equipment capable of simulating heat loads of 140kW per rack without deploying expensive GPU servers.<\/p>\n<p>In the demonstration room unveiled on the 30th of last month, liquid-cooling pipes and high-performance GPU servers were arranged side by side. The setup uses direct-to-chip (D2C) cooling, in which coolant is circulated through cold plates pressed against server chips, while autonomous robots moved between server racks collecting temperature, humidity and thermal-imaging data. In the integrated control room in the same building, the power and cooling equipment and network status of 12 data centers in the Seoul metropolitan area were being monitored in real time.<\/p>\n<p>The water-cooled load bank developed in-house by KT Cloud is the symbolic piece of equipment at the site. The server-type unit generates up to 64kW of heat load per 42U rack (8kW per unit), while the rack-type unit can simulate up to 140kW, targeting ultra-high-density racks on the order of Nvidia&#8217;s GB200 NVL72. Using actual GPU servers for testing carries the risk of damaging equipment worth hundreds of millions of won and adds cost, but the load bank can create identical heat conditions so that the stability of cooling equipment can be verified in advance.<\/p>\n<p>Lee Won-min, a KT Cloud manager who took part in the development, said, &#8220;It is easy to build a device that simply generates heat and cools it down,&#8221; adding that the company&#8217;s equipment was designed to reflect the cooling characteristics and operating conditions of actual GPU servers. KT Cloud has also used the equipment to complete load tests tailored to the actual usage standards of global customers.<\/p>\n<p>D2C liquid cooling has moved beyond the demonstration stage and been applied to commercial services. At the Gasan AIDC, KT Cloud is providing D2C cooling services to global hyperscaler customers. The company says this can cut cooling power consumption by 20-30% compared with air cooling. The cooling system is handled in-house from design through fluid analysis and performance verification, with risks such as leaks, corrosion and foreign matter checked in advance and reflected in the design of new centers. Immersion cooling, in which servers are submerged in a dielectric coolant, has also been separately demonstrated.<\/p>\n<p>Operating software was also developed in-house rather than purchased from outside vendors. Representative examples are &#8220;Pathfinder,&#8221; which analyzes power equipment in real time and identifies recovery paths in the event of a failure, and &#8220;DIMS Insight,&#8221; which uses AI to analyze equipment data and predict anomalies. Based on operational data accumulated over 25 years, the system identifies the likelihood of failure and the points requiring preemptive maintenance. Bang Jae-won, head of KT Cloud&#8217;s AIDC Business Development Team, said, &#8220;Solutions like DIMS were all developed by us in-house,&#8221; adding, &#8220;They were built by the people who actually run the operations, not purchased from outside.&#8221;<\/p>\n<p>Operational experience was also reflected in the building design. The Mokdong 2 Center is the first data center in Seoul to apply seismic isolation, with 84 isolation devices installed on the building&#8217;s second and a half floors. Key power and cooling equipment was placed on the third floor above ground in consideration of flood risk. Power is supplied dually from separate substations, and the power distribution rooms are spatially separated. If external power is cut, 12 diesel generators of 3,900kW each start automatically within 30 seconds and take over the load within one minute, and about 400,000 liters of reserve diesel allow roughly 48 hours of self-generation at current load levels.<\/p>\n<p>An &#8220;air tunnel&#8221; running from the fourth floor to the rooftop is a buffer space that draws in cold outside air to cool the server rooms. It operates when the outside temperature is below 15 degrees Celsius and automatically switches to other air-conditioning methods such as chillers above that. Through this, the company says it has improved power operating efficiency by about 30% compared with conventional data centers and lowered the power usage effectiveness (PUE) to around 1.4.<\/p>\n<p>This in-house technology development is a precondition for expanding supply. The data centers currently in operation total about 152MW, and most of that capacity has been sold, making it difficult to accommodate additional large-scale GPU customers. KT Cloud plans to secure more than 1GW of new capacity by 2031, separate from existing facilities. It will pursue new AIDC projects starting with Bucheon in 2027, followed by Gunsan, Cheongna and Ansan.<\/p>\n<p>The new centers will strengthen floor loading and power and cooling design to handle high-density GPU servers. Power consumption per AI server rack has jumped from around 2kW in the past to 30-150kW recently, with some forecasts that it will rise to as much as 600kW. KT Cloud is conducting joint research with LS Electric on power infrastructure for modular data centers, and is working with Vertiv on design optimization for power, liquid cooling and modular infrastructure. The Gunsan AIDC, scheduled for supply in 2028, will use modular infrastructure in which key equipment is pre-built and tested at a factory before being installed on site.<\/p>\n<p>Park Jae-woo, head of KT Cloud&#8217;s DC Business, said the company will expand data centers based on actual demand in line with KT Group&#8217;s gigawatt supply target and will respond as much as possible to the speed and volume of supply the market demands. Team head Bang said, &#8220;We believe we can turn the various operational experiences we have datafied, analyzed and organized with AI into a single product and offer it as a service to other customers who want to build and operate data centers.&#8221;<\/p>\n<p>The move shows that the center of gravity in the AI infrastructure race is shifting from securing servers to power, cooling and operational automation. Nvidia&#8217;s next-generation chip &#8220;Vera Rubin&#8221; is so expensive that it is cited at around 27.5 billion won (approximately $20.6 million) per rack, meaning that a failure to verify cooling equipment in advance can lead directly to large asset losses. Some observers say that if KT Cloud commercializes its verification capabilities as a sellable solution, it could become a new revenue source targeting corporate customers preparing to build data centers. However, securing 1GW of new capacity depends on variables such as site acquisition, power approval and long-term investment financing, so whether the plan proceeds as scheduled remains to be seen.<\/p>\n","protected":false},"excerpt":{"rendered":"KT Cloud is independently validating the cooling and power technologies at the heart of next-generation AI data centers&hellip;\n","protected":false},"author":2,"featured_media":210894,"comment_status":"","ping_status":"","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[2],"tags":[99673,99677,99675,99679,99678,31,36227,1549,99674,2295,12357,16213,43376,99676],"class_list":["post-210893","post","type-post","status-publish","format-standard","has-post-thumbnail","category-korea","tag-ai-innovation-center","tag-bucheon-aidc","tag-d2c-liquid-cooling","tag-dims-insight","tag-gunsan-aidc","tag-korea","tag-kt-cloud","tag-ls-electric","tag-mokdong-2-data-center","tag-nvidia","tag-pathfinder","tag-vera-rubin","tag-vertiv","tag-water-cooled-load-bank"],"_links":{"self":[{"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/posts\/210893","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/comments?post=210893"}],"version-history":[{"count":0,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/posts\/210893\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/media\/210894"}],"wp:attachment":[{"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/media?parent=210893"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/categories?post=210893"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.europesays.com\/korea\/wp-json\/wp\/v2\/tags?post=210893"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}